Command Set | Analog Input Alarm |
5013/5017/5017H/5017UH/5018/5018P
$aaSiCjAh
Name Read Alarm Mode
Description Returns the alarm mode for the specified channel in the
| specified |
Syntax | $aaSiCjAh(cr) |
| $ is a delimiter character. |
| aa (range |
| address of an |
| SiCj identifies the desired slot i (i : 0 to 3) and the |
| desired channel j (j : 0 to 7). |
| Ah is the Read Alarm Mode command. |
| h indicates alarm type and can have the value H = High |
| alarm, L = Low alarm |
| (cr) represents terminating character, carriage return |
| (0Dh) |
Response | !aas(cr) if the command was valid |
| There is no response if the system detects a syntax error |
| or communication error or if the specified address does |
| not exist. |
| ! delimiter character indicating a valid command was |
| received. |
| aa represents the |
| corresponding |
| s indicates alarm mode and can have the value M = |
| Momentary mode, L = Latching mode |
| (cr) represents terminating character, carriage return |
| (0Dh) |