Chapter 6
$aaSiCjAhU(data)
Example command: $03S0C1AHU+080.00(cr)
response: !03(cr)
Channel 1 of slot 0 in the ADAM-5000 system at
address 03h is configured to accept type-T thermocou-
ple input. The command will set its High alarm limit to
+80°C.
The system confirms the command has been received.
Note:
An analog input module requires a maximum of 2
seconds after it receives a Set Alarm Limit command
to let the settings take effect. During this interval,
the module cannot be addressed to perform any
other actions.
ADAM-5000 6-85