B.3 Analog Input Ranges - ADAM-5017H

Range

Input

Data Formats

+Full

Zero

 

-Full

Displayed

Code

Range

Scale

Scale

 

Resolution

 

 

 

 

 

 

 

 

 

 

 

00h

±10 V

Engineering

11

0

-11

 

2.7 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

EFFF

 

1

 

 

 

 

 

 

 

 

 

01h

0

~ 10 V

Engineering

11

0

Don't care

 

2.7 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

Don't care

 

1

 

 

 

 

 

 

 

 

02h

±5 V

Engineering

5.5

0

-5.5

 

1.3 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

EFFF

 

1

 

 

 

 

 

 

 

 

 

03h

0

~ 5 V

Engineering

5.5

0

Don't care

 

1.3 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

Don't care

 

1

 

 

 

 

 

 

 

 

04h

±2.5 V

Engineering

2.75

0

-2.75

 

0.67 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

EFFF

 

1

 

 

 

 

 

 

 

 

 

05h

0

~ 2.5 V

Engineering

2.75

0

Don't care

 

0.67 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

Don't care

 

1

 

 

 

 

 

 

 

 

06h

±1 V

Engineering

1.375

0

-1.375

 

0.34 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

EFFF

 

1

 

 

 

 

 

 

 

 

 

07h

0

~ 1 V

Engineering

1.375

0

Don't care

 

0.34 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

Don't care

 

1

 

 

 

 

 

 

 

 

08h

±500 mV

Engineering

687.5

0

-687.5

 

0.16 mV

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

EFFF

 

1

 

 

 

 

 

 

 

 

 

09h

0

~ 500

Engineering

687.5

0

Don't care

 

0.16 mV

mV

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

Don't care

 

1

 

 

 

 

 

 

 

 

 

0ah

4

~ 20 mA

Engineering

22

4.0

Don't care

 

5.3 µA

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

02E9

Don't care

 

1

 

 

 

 

 

 

 

 

 

0bh

0

~ 20 mA

Engineering

22

0

Don't care

 

5.3 µA

 

 

 

 

 

 

 

 

 

 

 

 

Two's Comp

0FFF

0

Don't care

 

1

 

 

 

 

 

 

 

 

 

Note: The full scale values in this table are theoretical values for your reference; actual values will vary.

B-8

ADAM-5000

Page 253
Image 253