Chapter 6
$aaSiCjB
Name Read Input Range
Description Returns the input range in engineering units for a
specified channel of a specified analog input module in a
specified system.
Syntax $aaSiCjB
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
SiCj identifies the slot i (i:0 to 3) of the ADAM-5000
system and the channel j (j:0 to 7) of the ADAM-5017H
/ 5017UH module you want to interrogate.
B represents the read input range command.
(cr) is the terminating character, carriage return (0Dh).
Response !aarr00(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
rr represents the 2-character hexadecimal code of the
input range. (See Appendix B)
(cr) is the terminating character, carriage return (0Dh).
ADAM-5000 6-61