Chapter 6
$aaSiCj1
Name 20 mA Calibration
Description Directs the specified channel to store parameters following a calibration for 20 mA output
Syntax | $aaSiCj1(cr) |
| $ is a delimiter character. |
| aa (range |
| address of the |
| SiCj identifies the I/O slot i (i : 0 to 3) and the channel |
| j (j : 0 to 3) of the module you want to calibrate. |
| 1 is the 20 mA calibration command. |
| (cr) is the terminating character, carriage return (0Dh) |
Response | !aa(cr) if the command is valid. |
| ?aa(cr) if an invalid operation was entered. |
| There is no response if the module detects a syntax error |
| or communication error or if the specified address does |
| not exist. |
| ! delimiter character indicating a valid command was |
| received. |
| ? delimiter character indicating the command was |
| invalid. |
| aa (range |
| address of an |
| (cr) is the terminating character, carriage return (0Dh) |
Note: | Before issuing the 20 mA Calibration command, the |
| analog output module should be trimmed to the |
| correct value using the Trim Calibration command. |
| Either a mA meter or a resistor and voltmeter should |
|
|