Command Set | 5017/5018 |
| Analog Input |
$aaSi9shhhh
Example command: $07S29+0042(cr)
response: !07(cr)
The command increases the CJC offset value of the analog input module in slot 2 of the system at address 07h with 66 counts (42 hex) which equals about 0.6°C.
Note: An analog input module requires a maximum of 2 seconds to perform auto calibration and ranging after it receives a CJC Calibration command. During this interval, the module cannot be addressed to perform any other actions.