Chapter 6
#aaSiCj
Name | Specified Analog Data In |
Description Returns the input value of a specified channel of a | |
| specified analog input module in a specified ADAM- |
| 5000 system in engineering units or two’s complement |
| data format |
Syntax | #aaSiCj(cr) |
| # is a delimiter character. |
| aa (range |
| address of the |
| configure. |
| Si identifies the I/O slot (i:0 to 3) of |
| you want to read. |
| Cj identifies the channel you want to read. |
| (cr) is the terminating character, carriage return (0Dh). |
Response | !(data)(cr) if the command is valid. (Engineering Unit |
| Data Format) |
!(dddd)(cr) if the command is valid. (Two’s Complement Data Format)
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or communication error or if the specified address does not exist.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
(data) is the input value in engineering units of the specified channel of the specified analog input module.