Chapter 6
#aaSiCj
Name Specified Analog Data In
Description Returns the input value of a specified channel of a
specified analog input module in a specified ADAM-
5000 system in engineering units or two’s complem ent
data format
Syntax #aaSiCj(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
configure.
Si identifies the I/O slot (i:0 to 3) of ADAM-5000 system
you want to read.
Cj identifies the channel you want to read.
(cr) is the terminating character, carriage return (0Dh).
Response !(data)(cr) if the command is valid. (Engineering Unit
Data Format)
!(dddd)(cr) if the command is valid. (Two’ s Complement
Data Format)
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
(data) is the input value in engineering units of the
specified channel of the specified analog input module.
ADAM-5000 6-69