Chapter 6

$aaSiCj4

 

Name

Start-Up Output Current/Voltage Configuration

Description Stores a default output value in a specified channel. The

 

output value will take effect upon startup or reset.

Syntax

$aaSiCj4(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system.

 

SiCj identifies the I/O slot i (i : 0 to 3) and the channel j (j

 

: 0 to 3) of the module you want to set.

 

4 is the Start-Up Output Current/Voltage Configuration

 

command.

 

(cr) is the terminating character, carriage return (0Dh)

Response

!aa(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

(cr) is the terminating character, carriage return (0Dh)