Command Set 5024 Analog Output

$aaSiCjArrff

Response

!aa(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax

 

error or communication error or if the specified address

 

does not exist.

 

! delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

(cr) is the terminating character, carriage return (0Dh)

Example

command: $35S3C0A3110(cr)

 

response: !35(cr)

 

The analog output channel 0 in slot 3 of the ADAM-

 

5000 system at address 35h is configured to an output

 

range 4 to 20mA, engineering units data format, and a

 

slew rate of 1.0mA/sec.

 

The response indicates that the command has been

 

received.

Note:

An analog output module requires a maximum of 20

 

milliseconds to perform auto calibration and ranging

 

after it is reconfigured. During this time span, the

 

module cannot be address to perform any other

 

actions.

6-92

ADAM-5000

Page 157