Command Set 5024 Analog Output
$aaSiCjArrff
Response | !aa(cr) if the command is valid. |
| ?aa(cr) if an invalid operation was entered. |
| There is no response if the module detects a syntax |
| error or communication error or if the specified address |
| does not exist. |
| ! delimiter character indicating a valid command was |
| received. |
| ? delimiter character indicating the command was |
| invalid. |
| aa (range |
| address of an |
| (cr) is the terminating character, carriage return (0Dh) |
Example | command: $35S3C0A3110(cr) |
| response: !35(cr) |
| The analog output channel 0 in slot 3 of the ADAM- |
| 5000 system at address 35h is configured to an output |
| range 4 to 20mA, engineering units data format, and a |
| slew rate of 1.0mA/sec. |
| The response indicates that the command has been |
| received. |
Note: | An analog output module requires a maximum of 20 |
| milliseconds to perform auto calibration and ranging |
| after it is reconfigured. During this time span, the |
| module cannot be address to perform any other |
| actions. |