Chapter 6
$aaSiAFFff
Name | Set Data Format |
Description Sets the data format in engineering units or in two's complement format for a specified analog input module in a specified system.
Syntax | $aaSiAFFff |
| $ is a delimiter character. |
| aa (range |
| address of the |
| configure. |
| Si identifies the I/O slot of the |
| containing the |
| configure. |
| AFF represents the set data format command. |
| ff represents the |
| data format. 00 is for engineering unit format. 02 is for |
| two’s complement format. |
Note: | Each channel in an |
| may be set to a different range, but the data formats |
| of all channels in this module must be the same. |
| (cr) is the terminating character, carriage return (0Dh). |
Response | !aa(cr) if the command is valid. |
| ?aa(cr) if an invalid operation was entered. |
| There is no response if the module detects a syntax error |
| or communication error or if the specified address does |
| not exist. |
| ! delimiter character indicating a valid command was |
| received. |
| ? delimiter character indicating the command was |
|
|