Command Set
5017/5018
Analog Input
#aaSiCj
Name Specified Analog Data In
Description Returns the input value of a specified channels for a
specified analog input module of a specified system in
engineering unit only.
Syntax #aaSiCj(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
Si identifies the I/O slot you want to interrogate.
Cj identifies the channel you want to read.
(cr) is the terminating character, carriage return (0Dh)
Response >(data) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
> is a delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
(data) is the input value in engineering units of the
specified channel for a specified analog input module of
the specified system. If (data) = “ ”, it means the
channel is invalid.
(cr) is the terminating character, carriage return (0Dh)
6-48 ADAM-5000