ADAM-5000 Series
Copyright Notice
Technical Support
Message to the Customer… Advantech Customer Services
Product Warranty
Page
Contents
ADAM-5013 RTD Input Command Set …
Appendix a Quick Start Example….….………………………. A-1
ADAM-5000 series main system’s DIP Switch
Figures
10 Execute Span Calibration……………………...…..5-17
Introduction
Overview
Configuration
Module
Software Utility
System Configuration
Understand the Troubleshooting Procedures
Review the installation Guideline
Understand the System Kernel
Understand the Utility Software
Installation Guideline
Power Requirements
General Environmental Specifications
Chapter
Setting the Network Address Switch
Dimensions and WeightsADAM-5000
Dimensions and WeightsADAM-5000E
I/O Slots and I/O channel Numbering
Module Installation
Panel Mounting
Mounting
ADAM-5000Rail mounting
DIN Rail Mounting
DC Power Supply Unit Wiring
Wiring and Conections
7ADAM-5000 Wiring Connections
Module Wiring
RS-485 Port Connection
RS-232 Port Connection
8Build-in Communication Ports for Diagnostic Connection
9Flexible Communication Port Function Connection
ADAM-5000 System
CPU’s Basic Functions
ADAM-5000 System Overview
Way Isolation and Watchdog Timer
Remote Software Configuration and Calibration
Flexible Alarm Setting
Connectivity and Programming
ADAM-5000 System
Flexible Communication PortADAM-5000E only
Flexible Communication Connection
Single System Setup thru the RS-232 Port
System Setup
ADAM-5000
Function block diagram
Modules
I/O Module Support List
Software Utilities
ADAM-4000 and ADAM-5000 Windows Utility
Save Function
Chapter Overview Main Menu
1Display the connected module
COM Port Settings
Prefix Char
Chapter
ADAM-5000
Chapter Terminal Emulation
Data Scope
4Checksum function enabled
Address of selected modules
Saving module’s Configuration to file
Chapter
Load Module’s Configuration File
ADAM-5000
Module Configuration
Zero Calibration
Module Calibration
7Zero Calibration
ADAM-5000
12 Execute CJC Calibration
Digital Output Module
Software Utilities
Digital Filter
Chapter Alarm Setting
Download Procedure
Choose the baud rate Choose Download file
Firmware downloads in progress Firmware downloads complete
DDE Dynamic Data Exchange Server
Chapter DLL Dynamic Link Library Driver
Software Utilities
Command Set
Syntax
Introduction
Chapter
CPU
CPU Command Set
Name
Aannccff
Syntax Aannccffcr
Response
1Baud rate codes
Example command %23000A40cr
Syntax $aa2cr
$aa2
Command SetCPU
Syntax $aaMcr
$aaM
#aaF
Example command $15Mcr response !155000cr
Syntax $aaFcr
$aaF
CPU
Syntax $aaTcr
$aaT
$aaT
Syntax $aa5cr
$aa5
$aa5
Example command $395cr
Syntax $aaEcr
$aaE
2Analog module error codes
ADAM-5013 RTD Input Command Set
Command Set RTD Input
Syntax $aaSiArrffcr
$aaSiArrff
$aaSiArrff
Example command $35S3A2000cr
Syntax $aaSiBcr
$aaSiB
RTD Input
Example command $35S3Bcr response !352000cr
Syntax $aaSicr
$aaSi
Example command $35S3cr Response +80.01 +20.00 -40.12cr
Syntax $aaSiCjcr
$aaSiCj
$aaSiCj
Example command $35S3C0cr response +80.01cr
Syntax $aaSiERcr
$aaSiER
$aaSi5mm
Example command $00S1501cr
Syntax $aaSi6cr
$aaSi6
Example command $00S16cr
$aaSi0
Name RTD Span Calibration
Syntax $aaSi0cr
Syntax $aaSi1cr
$aaSi1
Syntax $aaSi2cr
$aaSi2
Analog Input Command Set
Command Set 5017/5018 Analog Input
Example
$35S3A0000cr
35cr
Si identifies the I/O slot you want to read
Example command $26S1B
Syntax $aaSi5mmcr
Example command $00S1581cr
Aammcr if the command is valid
Example command $02S16cr
Name All Analog Data
#aaSi
Syntax #aaSicr
Response Datadatadatadatadatadatadatadatacr if
$aaSi
Syntax #aaSiCjcr
#aaSiCj
Example command #22S2C2cr
Name Initialize Eeprom data
Syntax $aaSiØcr
$aaSiØ
Command Set 5017/5018
Syntax $aaSi3cr
$aaSi3
Example command $09S13cr response +0036.8cr
Syntax $aaSi9shhhhcr
$aaSi9shhh
$aaSi9shhhh
Example command $07S29+0042cr
ADAM-5017H/ADAM-5017UH Analog Input Command Set
Command Set 5017H/5017UH Analog Input
Syntax $aaSiCjArrFF
$aaSiCjrrFF
Response !35cr
Example Command $35S3C1A0bFFcr
Syntax $aaSiCjB
$aaSiCjB
$aaSiCjB
Example Command $35S3C1Bcr Response !350b00cr
Syntax $aaSiAFFff
$aaSiAFFff
Example command $35S3AFF00cr
Syntax $aaSiB
Example command $35S3Bcr response !35FF00cr
Syntax #aaSi
Command Set 5017H/5017UH Analog Input
Specified analog input module in a specified Adam
#aaSiCj
Example command #35S3C2cr response +9.750 cr
Analog Input Alarm Command Set
Syntax $aaSiCjAhscr
5013/5017/5017H/5017UH/5018/5018P
$aaSiCjAhs
Example command $03S0C1AHLcr
Syntax $aaSiCjAhcr
$aaSiCjAh
Example command $03S0C1ALcr
Syntax $aaSiCjAhEscr
$aaSiCjAhEs
Example command $03S0C1ALEEcr
Syntax $aaSiCjChcr
$aaSiCjCh
Example command $03S0C1CLcr
Syntax $aaSiCjAhCSkCncr
$aaSiCjAhSkCn
$aaSiCjAhCSkCn
Example command $03S0C1ALCS1C0cr
Syntax $aaSiCjRhCcr
$aaSiCjRhc
Example command $03S0C1RLCcr response !03S1C0cr
Syntax $aaSiCjAhUdatacr
$aaSiCjAhUdata
Example command $03S0C1AHU+080.00cr
Syntax $aaSiCjRhUcr
$aaSiCjRhU
$aaSiCjRhU
Example command $03S0C1RHUcr response !03+2.0500cr
Syntax $aaSiCjScr
$aaSiCjS
Example command $03S0C1Scr
Analog Output Command Set
Command Set Analog Output
Syntax $aaSiCjArrffcr
$aaSiCjArrff
Example Command $35S3C0A3110cr
Command Set 5024 Analog Output
Syntax $aaSiCjBcr
Analog Output
Example command $24S1C1B
Syntax #aaSiCjdatacr
$aaSiCjdata
#aaSiCjdata
Example command #33S1C115.000cr
Syntax $aaSiCj4cr
$aaSiCj4
Example command $0AS1C14cr
Syntax $aaSiCj0cr
$aaSiCj0
100 ADAM-5000
Syntax $aaSiCj1cr
$aaSiCj1
102 ADAM-5000
Syntax $aaSiCj3hhcr
$aaSiCj3hh
Example command $07S1C2314cr
Syntax $aaSiCj6cr
$aaSiCj6
Example command $0AS2C16cr response !0A03.000cr
Digital Input/Output
Aadatainputdataoutput00cr if the command is valid
Aadataoutputdataoutput00cr if the command is valid
Aadataoutput0000cr if the command is valid
Example command $33S26cr response !33112200cr
$aaSiBBdata
Command Set 5060/5068/5069 Digital I/O
Example Command #15S11201cr
Command #15S0003Acr
Command #14S1001234cr
Name Read Channel Masking Status
$aaSiM
Example command $19S1Mcr response !191322cr
ADAM-5080 Counter/Frequency Command Set
Command Set
ADAM-5000 117
AaFFFFFFFFcr if the command is valid
Command $25Tcr
$aaF
Response !18A2.3cr
Eample
$aaSiArrff
Example command $24S1A0002cr
Rr=02
Example command $35S3Bcr response !350100cr
Response Data data data data
1235458013, 2675213069, 3452146305
Example command #16S2cr
0e88fa63c33697b52a68d61fe2ca6915cr
0e88fa63,c33697b5,2a68d61f,e2ca6915
Actual frequency = 98700/100 =
0000098700,0000064900,0000076200,0000011600
0000F1000002000000031000000DD400cr
0000F100,00020000,00031000,000DD400
$aaSiCj
#aaSiCj
Syntax $aaSiØdatacr
$aaSiØdata
Example command $26S3000765cr
Description
Example command $26S30cr response !2600765cr
Command Set Counter Frequency Module
Syntax $aaSiCj5scr
$aaSiCj5s
Example command $26S3C251cr
Syntax $aaSiCj5cr
$aaSiCj5
Example command $26S3C25cr
Clear Counter
Example command $26S3C26cr response !26cr
Syntax $aaSi7cr
$aaSiCj7
Command Set
Syntax @aaSiCjPdatacr
$aaSiCjPdata
Example command @26S3C2P0000004369cr
Syntax @aaSiCjGcr
$aaSiCjPG
$aaSiCjG
Example command @26S3C2Gcr response !260000004369cr
Set Alarm Disable/Latch
Example command $03S0C1ALEDcr
Command Set Counter
Read Alarm Disable/Latch
Example command $03S0C1ALcr
Clear Alarm Status
Example command $03S0C1CLcr
$aaSiCAhCSkCh
Example command $03S0C1ALCS1C0cr response !03cr
RhC is the command for reading Alarm Connection
Example command $03S0C1RLCcr response !03SØC1cr
Value is from 0 to 4294967295. Be aware that data has
Example command $03SØC1AHU0000000020cr response !03cr
Format is always in engineering units. Be aware that
Example command $03SØC1RHUcr response !030000000026cr
Alarm occurred, ‘0’ means it did not occur
Example command $03SØC1S
Troubleshooting
Software Diagnosis
Hardware Diagnosis
POW Indicator
System Indicators
Incorrect External Power
Faulty Power Supply
Device or Module causing Power Supply to Shutdown
Communication Problems
RUN Indicator
Some Quick Steps
I/O Module Troubleshooting
Quick Start Example
System Requirement to setup an ADAM-5000 System
Power Supply
Appendix a
Host Computer
Power Supply
Communication Wiring
Adam Utility Software
Basic Configuration Hook-up
Adam Isolated RS-232/RS-485 Converter optional
Adam Repeater optional
Configuration with the Adam Utility software
Default Factory Settings
Example
Baud Rate and Checksum
Changing Baud Rate and Checksum
INIT* state defaults
Figure A-3Grounding the INIT* terminal
Figure A-4ADAM-5000 network system hook-up
Distributed ADAM-5000 Network System Hook-up
This page intentionally left blank
Data Formats And I/O Ranges
Data Formats and I/O Ranges
Analog Input Formats
Engineering Units
Appendix B
LSB
Analog Input Ranges ADAM-5018
0000
ADAM-5000
Adam
Analog Input Ranges ADAM-5017H
Analog Input Ranges ADAM-5017UH
Analog Ontput Formats
Example
Analog Ontput Ranges
ADAM-5013 RTD Input Format and Ranges
Data Formats and I/O Ranges
RS-485 Network
RS-485 Network
Appendix C
Basic Network Layout
Daisychain
Figure C-2 Star structure
Star Layout
Figure C-3 Random Sstructure
Random
Figure C-4ADAM-4000 and ADAM-5000 in a network
Line Termination
Example
Figure C-5Signal distortion
Figure C-6Termination resister locations
Intelligent RS-485 Control
RS-485 Data Flow Control
This page intentionally left blank
Checksum Feature
How to Use
Checksum Enable/Disable
How to Use the Checksum Feature
Response !07+2.0500D8cr where
Appendix D
Printable Ascii Characters
Appendix E ADAM-4000/5000 System Grounding Installation
Grounding Scheme
ADAM-4000/5000 System Grounding Installation
External DI,DO,AI,AO Wiring Reference
Requirements for RS-485 signal wires
Appendix E
Figure E-4 Grounding for signal wires
Figure E-5 Grounding Reference
Some Suggestions on Wiring Layout
Appendix F Grounding Reference
Grounding Reference
Field Grounding and Shielding Application Overview
Appendix F
Grounding
Earth for reference
Figure F-2 Grounding Bar
Frame Ground and Grounding Bar
3The Frame Ground and Grounding Bar
Figure F-3 Normal mode and Common mode
Figure F-4 Normal mode and Common mode
Figure F-5 The purpose of high voltage transmission
Wire impedance
Figure F-7 Single point groundF.1
Single Point Grounding
Shielding Cable Shield
More cable, but more stable system
Figure F-10 Double isolated cable
Figure F-11 System Shielding
System Shielding
Figure F-12 The characteristic of the cable
Figure F-13 System Shielding1
Noise Reduction Techniques
Figure F-15 Noise Reduction Techniques
Check Point List
Grounding Reference
ADAM-5000 I/O Modbus Mapping Table
ADAM-5000 series main system’s DIP Switch Setting
Modbus Commands for 5000 Series
ADAM-5000 I/O Modbus Mapping Table
Modbus Address Mapping
410030 Slot4 End Addr
410117~ Reserved 410150
Address mapping of ADAM-5080 For ADAM-5000 ModBus