Advantech 5000 Series user manual Name All Analog Data, Syntax #aaSicr

Models: 5000 Series

1 301
Download 301 pages 22 Kb
Page 111
Image 111

Command Set

5017/5018

 

 

Analog Input

#aaSi

 

 

Name

All Analog Data In

 

Description Returns the input value of all channels for a specified analog input module of a specified system in engineer- ing unit only.

Syntax

#aaSi(cr)

 

# is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system you want to

 

interrogate.

 

Si is the I/O slot of ADAM-5000 system you want to

 

read.

 

(cr) is the terminating character, carriage return (0Dh)

Response

>(data)(data)(data)(data)(data)(data)(data)(data)(cr)if

 

the command is valid.

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

> is a delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

(data) is the input value in engineering units of a channel in the interrogated module of the specified system. The (data) from all channels is shown in sequence from 7 to

0.If (data) = “ ”, it means the channel is invalid. (cr) is the terminating character, carriage return (0Dh)

6-46

ADAM-5000

Page 111
Image 111
Advantech 5000 Series user manual Name All Analog Data, Syntax #aaSicr, Response Datadatadatadatadatadatadatadatacr if