Command Set | 5017/5018 | |
|
| Analog Input |
#aaSi |
|
|
Name | All Analog Data In |
|
Description Returns the input value of all channels for a specified analog input module of a specified system in engineer- ing unit only.
Syntax | #aaSi(cr) |
| # is a delimiter character. |
| aa (range |
| address of the |
| interrogate. |
| Si is the I/O slot of |
| read. |
| (cr) is the terminating character, carriage return (0Dh) |
Response | >(data)(data)(data)(data)(data)(data)(data)(data)(cr)if |
| the command is valid. |
| ?aa(cr) if an invalid operation was entered. |
| There is no response if the module detects a syntax error |
| or communication error or if the specified address does |
| not exist. |
| > is a delimiter character indicating a valid command was |
| received. |
| ? delimiter character indicating the command was |
| invalid. |
(data) is the input value in engineering units of a channel in the interrogated module of the specified system. The (data) from all channels is shown in sequence from 7 to
0.If (data) = “ ”, it means the channel is invalid. (cr) is the terminating character, carriage return (0Dh)