Data Formats and I/O Ranges
B.2 Analog Input Ranges - ADAM-5018
Module Range
Code
Input
Range
Description
Data
Formats +F.S. Zero -F.S. Displayed
Resolution Actual
Value
Engineering
Units +15.000 ±00.000 -15.000 1 µV
% of FSR +100.00 ±000.00 -100.00 0.01%
00h ±15 mV
Two's
Complement 7FFF 0000 8000 1 LSB
Reading/
1000
Engineering
Units +50.000 ±00.000 -50.000 1 µV
% of FSR +100.00 ±000.00 -100.00 0.01%
01h ±50 mV
Two's
Complement 7FFF 0000 8000 1 LSB
Reading/
100
Engineering
Units +100.00 ±000.00 -100.00 10 µV
% of FSR +100.00 ±000.00 -100.00 0.01%
02h ±100 mV
Two's
Complement 7FFF 0000 8000 1 LSB
Reading/
100
Engineering
Units +500.00 ±000.00 -500.00 10 µV
% of FSR +100.00 ±000.00 -100.00 0.01%
03h ±500 mV
Two's
Complement 7FFF 0000 8000 1 LSB
Reading/
10
Engineering
Units +1.0000 ±0.0000 -1.0000 100 µV
% of FSR +100.00 ±000.00 -100.00 0.01%
04h ±1 V
Two's
Complement 7FFF 0000 8000 1 LSB
Reading/
10000
Engineering
Units +2.5000 ±0.0000 -2.5000 100 µV
% of FSR +100.00 ±000.00 -100.00 0.01%
05h ±2.5 V
Two's
Complement 7FFF 0000 8000 1 LSB
Reading/
10000
Engineering
Units +20.000 ±00.000 -20.000 1 µA
% of FSR +100.00 ±000.00 -100.00 0.01%
06h ±20 mA
Two's
Complement 7FFF 0000 8000 1 LSB
Reading/
1000
ADAM-5018
07h Not Used
B-4 ADAM-5000