Command Set | Analog Input Alarm | |
5013/5017/5017H/5017UH/5018/5018P | ||
|
| |
$aaSiCjAhU(data) |
| |
Name | Set Alarm Limit |
|
Description Sets the High/Low alarm limit value for the specified | ||
| input channel of a specified | |
Syntax | $aaSiCjAhU(data)(cr) |
|
| $ is a delimiter character. | |
| aa (range | |
| address of an | |
| SiCj identifies the desired slot i (i : 0 to 3) and the | |
| desired analog input channel j (j : 0 to 7). | |
| AhU is the Set Alarm Limit command. | |
| h indicates alarm type and can have the value H = High | |
| alarm, L = Low alarm |
|
| (data) represents the desired alarm limit setting. The | |
| format is always in engineering units. | |
| (cr) represents terminating character, carriage return | |
| (0Dh) |
|
Response | !aa(cr) if the command was valid | |
| There is no response if the system detects a syntax error | |
| or communication error or if the specified address does | |
| not exist. |
|
! delimiter character indicating a valid command was received.
aa represents the
(cr) represents terminating character, carriage return (0Dh)