Command Set
Analog Input Alarm
5013/5017/5017H/5017UH/5018/5018P
$aaSiCjAhU(data)
Name Set Alarm Limit
Description Sets the High/Low alarm limit value for the specified
input channel of a specified ADAM-5000 system.
Syntax $aaSiCjAhU(data)(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
SiCj identifies the desired slot i (i : 0 to 3) and the
desired analog input channel j (j : 0 to 7).
AhU is the Set Alarm Limit command.
h indicates alarm type and can have the value H = High
alarm, L = Low alarm
(data) represents the desired alarm limit setting. The
format is always in engineering units.
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(cr) if the command was valid
There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.
(cr) represents terminating character, carriage return
(0Dh)
6-84 ADAM-5000