Command Set

Analog Input Alarm

5013/5017/5017H/5017UH/5018/5018P

$aaSiCjCh

Name

Clear Latch Alarm

Description Sets the High/Low alarm to OFF (no alarm) for the

 

specified input channel in the addressed ADAM-5000

 

system

Syntax

$aaSiCjCh(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

SiCj identifies the desired slot i (i : 0 to 3) and the

 

desired channel j (j : 0 to 7).

 

Ch is the Clear Latch Alarm command.

 

h indicates alarm type and can have the value H = High

 

alarm, L = Low alarm

 

(cr) represents terminating character, carriage return

 

(0Dh)

Response

!aa(cr) if the command was valid

 

There is no response if the system detects a syntax error

 

or communication error or if the specified address does

 

not exist.

! delimiter character indicating a valid command was received.

aa represents the 2-character hexadecimal address of the corresponding ADAM-5000 system.

(cr) represents terminating character, carriage return (0Dh)

6-78

ADAM-5000

Page 143
Image 143