Chapter 6

$aaSiCj6

Name

Clear Counter

Description Clear the counters of the specified counter/frequency

 

module

Syntax

$aaSiCj6(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system.

 

SiCj identifies the I/O slot i and the channel

 

j for the module you want to return a prior value.

 

6 is the command for clearing counter.

 

(cr) is the terminating character, carriage return (0Dh)

Response

!aa(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error or communication error or if the specified address does not exist.

! delimiter character indicating a valid command was received.

? delimiter character indicating the command was invalid.

aa (range 00-FF) represents the 2-character hexadecimal address of an ADAM-5000 system.

(cr) is the terminating character, carriage return (0Dh)

ADAM-5000

6-139

Page 204
Image 204