Command Set

5050/5051/5052/5055/5056

 

5060/5068/5069 Digital I/O

 

 

command: #14S1001234(cr)

response: >(cr)

An output byte with value 1234h (0001001000110100) is sent to the digital output module (ADAM-5056) in slot 1 of the ADAM-5000 system at address 14h. Channels 2, 4, 5, 9 and 12 will be set to ON, and all other channels are set to OFF.

command: #15S0003A(cr)

response: >(cr)

An output byte with value 3Ah (00111011) is send to the digital output module (ADAM-5060) in slot 0 of the ADAM-5000 system at address 15h. Channels 0, 1, 3, 4 and 5 will be set to ON while channel 2 is set to OFF. Bits 6 and 7 are not used and always default to 0.

Note: If any channel of the digital output module is config- ured as the output for an analog input alarm, it cannot be reconfigured via digital output commands. Channels used for analog input alarms always have a higher priority.