Command Set
5050/5051/5052/5055/5056
5060/5068/5069 Digital I/O
command: #14S1001234(cr)
response: >(cr)
An output byte with value 1234h (0001001000110100) is
sent to the digital output module (ADAM-5056) in slot 1
of the ADAM-5000 system at address 14h. Channels 2,
4, 5, 9 and 12 will be set to ON, and all other channels are
set to OFF.
command: #15S0003A(cr)
response: >(cr)
An output byte with value 3Ah (00111011) is send to the
digital output module (ADAM-5060) in slot 0 of the
ADAM-5000 system at address 15h. Cha nnels 0, 1 , 3, 4
and 5 will be set to ON while channel 2 is set to OFF. Bits
6 and7 are not used and alwaysdefault to 0.
Note:
If any channel
of the digital
output
module
is config-
ured
as the output for
an analog
input alarm,
it cannot
be reconfigured via
digital output commands.
Channels used for analog input alarms always have a
higher
priority.
6-112
ADAM-5000