Chapter 6
$aaSiCjRhU
Name Read Alarm Limit
Description Return the High/Low alarm limit value for the specified
| input channel in the addressed |
Syntax | $aaSiCjRhU(cr) |
| $ is a delimiter character. |
| aa (range |
| address of an |
| SiCj identifies the desired slot i and the desired channel |
| j. |
| RhU is the Read Alarm Limit command. |
| h indicates alarm type and can have the value H = High |
| alarm, L = Low alarm |
| (cr) represents terminating character, carriage return |
| (0Dh) |
Response | !aa(data)(cr) if the command was valid |
| There is no response if the system detects a syntax error |
| or communication error or if the specified address does |
| not exist. |
| ! delimiter character indicating a valid command was |
| received. |
| aa represents the |
| corresponding |
| (data) represents the desired alarm limit setting. The |
| format is always in engineering units. Be aware that |
| (data) has 10 characters. |
| (cr) represents terminating character, carriage return |
| (0Dh) |