| Command Set | 5017/5018 |
| |
|
|
| Analog Input | |
| $aaSi5mm |
|
| |
| Name | Enable/Disable Channels for multiplexing | ||
| Description Enables/Disables multiplexing for separate channels of | |||
|
| the specified input module | ||
| Syntax | $aaSi5mm(cr) |
|
|
|
| $ is a delimiter character. |
|
|
|
| aa (range | ||
|
| address of the | ||
|
| Si identifies the I/O slot of the system. | ||
|
| 5 identifies the enable/disable channels command. | ||
|
| mm are two hexadecimal values. Each value is interpret- | ||
|
| ed as 4 bits. The first | ||
|
| channels | ||
|
| status of channels | ||
|
| is disabled, while a value of 1 means the channel is | ||
|
| enabled. (See the Read Channel Status Command | ||
|
| $aaSi6) |
|
|
| Note: | Bit 7 cannot be enabled in the | ||
|
| since the module is physically limited to 7 channels. | ||
|
| (cr) is the terminating character, carriage return (0Dh) | ||
| Response | !aa(cr) if the command is valid. | ||
|
| ?aa(cr) if an invalid operation was entered. | ||
|
| There is no response if the module detects a syntax error | ||
|
| or communication error or if the specified address does | ||
|
| not exist. |
|
|
|
| ! delimiter character indicating a valid command was | ||
|
| received. |
|
|
|
| ? delimiter character indicating the command was | ||
|
| invalid. |
|
|
|
|
|
|
|
|
| |||