Chapter 6

$aaSiCjrrFF

Name Set Input Range

Description Sets the input range for a specified channel of a speci- fied analog input module in a specified system.

Syntax

$aaSiCjArrFF

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system you want to

 

configure.

 

SiCj identifies the slot i (i:0 to 3) of the ADAM-5000

 

system and the channel j (j:0 to 7) of the ADAM-5017H

 

/ 5017UH whose range you want to set.

 

A represents the set input range command.

 

rr represents the 2-character hexadecimal code of the

 

input range. (See Appendix B)

Note:

Each channel in a ADAM-5017H / 5017UH module may

 

be set to a different range, but the data formats of all

 

channels in this module must be the same.

 

(cr) is the terminating character, carriage return (0Dh).

Response

!aa(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

 

ADAM-5000

6-59

Page 124
Image 124
Advantech 5000 Series user manual $aaSiCjrrFF, Syntax $aaSiCjArrFF