Command Set

5080 Counter/

Frequency Module

 

$aaF

 

 

 

Name

Read Firmware Version

 

 

Description Returns the firmware version code from a specified

 

 

ADAM-5000 system.

 

 

Syntax

$aaF(cr)

 

 

 

$ is a delimiter character.

 

 

 

aa (range 00-FF) represents the 2-character

 

 

hexadecimal address of the ADAM-5000 system you

 

 

want to interrogate.

 

 

 

F is the command for reading Firmware Version.

 

 

(cr) is the terminating character, carriage return (0Dh).

 

Response

!aa(version)(cr) if the command is valid.

 

 

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error, communication error or if the specified address does not exist.

! delimiter character indicating a valid command was received.

? delimiter character indicating the command was invalid.

aa (range 00-FF) represents the 2-character hexadecimal address of an ADAM-5000 system.

(version) represents the firmware version of the ADAM-5000 system.

(cr) is the terminating character, carriage return (0Dh).

6-120