Panel Calibration
The request to touch the crosshairs is the first
Calibration successful is the second
calibration of the touch device
FIG. 89 Touch Panel Calibration Screens
If the calibration was improperly set and you cannot return to the Calibration page (through the panel’s firmware); you can then access this firmware page via G4 WebControl where you can navigate to the Protected Setup page and press the Calibrate button through your VNC window.
This action causes the panel to go to the Calibration page seen above, where you can physically recalibrate the actual touch panel again using the above procedures.
Testing your Calibration
1.Press and hold down the
FIG. 90 Calibration Test page
2.Press anywhere on this page to confirm the
3.If the crosshairs do not appear directly below your LCD touch points, press the Back button and recalibrate the panel using the above steps.
Peel the protective plastic film from the LCD.
If the protective plastic film on the LCD is not removed, the panel may not respond properly to touch points on the LCD nor allow proper screen calibration.
4.Exit this Calibration Test page by pressing the Back button to return to the Protected Setup page.
If Calibration Is Not Working
Cycling power to the panel should provide a baseline calibration for the particular touch panel.