Panel Calibration
Panel Calibration
This section outlines the steps for calibrating the touch panel. It is recommended that you calibrate the panel both before its initial use and after completing a firmware download.
Modero panels are factory setup with specific demo touch panel pages. The first splash screen that appears indicates the panel is receiving power, beginning to load firmware, and preparing to display the default touch panel pages. When the panel is ready, the AMX Splash Screen is replaced by the Initial Panel Page (FIG. 87).
AMX Splash Screen | Initial Panel Page |
(appears during | (AMX Logo Page) |
FIG. 87 AMX splash screen and initial Panel Page |
|
Calibrating the MVP Panels
1.Press and hold the two lower external pushbuttons on both sides of the MVP (FIG. 88) for 6 seconds to
Setup Access buttons |
(bottom button on each side) |
3 second press/hold of both buttons: Opens the Setup page
6 second press/hold of both buttons: Opens the Calibration page
FIG. 88 Location of Setup Access buttons
2.Using the included stylus, press the crosshairs (on the Calibration page) to set the calibration points on the LCD (FIG. 89).
3.After the "Calibration Successful." message appears, press anywhere on the screen to continue and return to the Setup page.