| Chapter 4 Parameters |
Pr.97 | Preset Count Down Completion |
|
| Settings 00 to 9999 | Factory Setting: 00 |
This parameter sets a preliminary count value for the internal counter. Counter is incremented
by a
M2 (see Pr.44 or Pr.45, setting 14). Count starts at 01. Upon completion the selected Multi-
Function Output Terminal will close. Preliminary Count could be used to initiate an external
event before the “terminal count” is reached. (See Pr.38, 39, 40, 41, 42, 45, and 46 for further
details.)
Pr.98 | Total Time Count from Power On (Days) |
| |
| Settings | 00 to 65535 days | Read Only |
Pr.99 | Total Time Count from Power On (Minutes) |
| |
| Settings | 00 to 1440 minutes | Read Only |
Pr.100 | Software Version | Read Only |
This parameter shows the software version for the AC motor drive.
Pr.101 | Auto Acceleration/Deceleration |
Factory Setting: 00
Settings 00 Linear acceleration/deceleration
01Auto acceleration, linear deceleration
02Linear acceleration, auto deceleration
03Auto acceleration/deceleration
04Linear Accel/Decel Stall Prevention during Deceleration
(Please refer to Accel/Decel time setting at parameter
When this parameter is set to 03, the AC drive will accel/decel in the fastest and smoothest
possible way by automatically adjusting the accel /decel time.
This parameter provides five modes to choose:
00Linear acceleration and deceleration (operation by Pr.10, Pr.11, or Pr.12, Pr.13 acceleration/deceleration time)
01Automatic acceleration, linear deceleration (Operation by automatic acceleration, Pr.11 or Pr.13 deceleration time).
Revision May 2008, ME14, SW V3.04 |