Chapter 4 Parameters

Pr.97

Preset Count Down Completion

 

 

Settings 00 to 9999

Factory Setting: 00

This parameter sets a preliminary count value for the internal counter. Counter is incremented

by a low-to-high transition on one of the programmed Multi-Function Input Terminals: M1 or

M2 (see Pr.44 or Pr.45, setting 14). Count starts at 01. Upon completion the selected Multi-

Function Output Terminal will close. Preliminary Count could be used to initiate an external

event before the terminal countis reached. (See Pr.38, 39, 40, 41, 42, 45, and 46 for further

details.)

Pr.98

Total Time Count from Power On (Days)

 

 

Settings

00 to 65535 days

Read Only

Pr.99

Total Time Count from Power On (Minutes)

 

 

Settings

00 to 1440 minutes

Read Only

Pr.100

Software Version

Read Only

This parameter shows the software version for the AC motor drive.

Pr.101

Auto Acceleration/Deceleration

Factory Setting: 00

Settings 00 Linear acceleration/deceleration

01Auto acceleration, linear deceleration

02Linear acceleration, auto deceleration

03Auto acceleration/deceleration

04Linear Accel/Decel Stall Prevention during Deceleration

(Please refer to Accel/Decel time setting at parameter Pr.10-Pr.13)

When this parameter is set to 03, the AC drive will accel/decel in the fastest and smoothest

possible way by automatically adjusting the accel /decel time.

This parameter provides five modes to choose:

00Linear acceleration and deceleration (operation by Pr.10, Pr.11, or Pr.12, Pr.13 acceleration/deceleration time)

01Automatic acceleration, linear deceleration (Operation by automatic acceleration, Pr.11 or Pr.13 deceleration time).

Revision May 2008, ME14, SW V3.04

4-73

Page 108
Image 108
Delta Electronics VFD-M manual Pr.97, Pr.98, Pr.99, Pr.100, Pr.101 Auto Acceleration/Deceleration