Chapter 4 Parameters
Pr.24 | Reverse Operation Inhibition |
Factory Setting: 00
Settings 00 Enable REV operation 01 Disable REV operation
This parameter is used to disable motor rotation in reverse.
Pr.25
Settings 115V/230V series | Factory Setting: 390 | ||
| 460V series | Factory Setting: 780 | |
| 575V series | Factory Setting: 975 | |
| 00 disable |
|
|
|
|
|
|
During deceleration, the DC bus voltage may exceed its maximum allowable value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating, and maintain a constant output frequency to prevent from
Note: In applications where inertia is low,
|
| DC bus voltage |
|
|
|
| |
|
| detection |
|
|
| level |
|
|
| time |
|
|
| output |
|
|
| Freq. |
|
|
| time | |
|
|
| |
Pr.26 | Unit: 1% | ||
|
|
| Factory Setting: 150% |
| Settings | 20 to 200% |
|
|
| 00 disable |
|
A setting of 100% is equal to the Rated Output Current of the drive. |
| ||
Revision May 2008, ME14, SW V3.04 |