Chapter 4 Parameters
This parameter sets the Ac drive address identification when using the
communication.
Pr.89 | Transmission Speed (Baud rate) |
Factory Setting: 01
Settings 00 4800 bps
019600 bps
0219200 bps
0338400 bps
This parameter sets the transmission speed for communication on the
Pr.90 Transmission Fault Treatment
Factory Setting: 03
Settings 00 Warn and Continue Operating
01Warn and RAMP to Stop
02Warn and COAST to Stop
03Keep Operation without Warning
Pr.91 Time Out Detection
Factory Setting: 0.0
Settings 0.1 to 120.0 sec 0.0 disable
This parameter is used for ASCII mode. When the
separation between characters cannot exceed 500 ms.
Pr.92 | Communication Protocol |
Factory Setting: 00
Settings 00 Modbus ASCII mode, <7,N,2>
01Modbus ASCII mode, <7,E,1>
02Modbus ASCII mode, <7,O,1>
03Modbus RTU mode, <8,N,2>
04Modbus RTU mode, <8,E,1>
05Modbus RTU mode, <8,O,1>
1.Computer Control