Chapter 4 Parameters
Pr.60 |
Factory Setting: 00
Settings 00
01Enabled during constant speed operation until the allowable time for detection (Pr.62) elapses.
02 Enabled during constant speed operation and halted after detection.
03Enabled during acceleration until the allowable time for detection (Pr.62) elapses.
04 Enabled during acceleration and halted after detection.
| Pr.61 | Unit: 1% | |
|
| Settings 30 to 200% | Factory Setting: 150 |
A setting of 100% is proportional to the Rated Output Current of the drive.
This parameter sets the
current is equal to 100%.)
| Pr.62 | Unit: 0.1 sec | |
|
| Settings 0.0 to 10.0sec | Factory Setting: 0.1sec |
This is the duration for
torque detection level (Pr.61), an
(Please refer to Pr. 45 and Pr.46)
Pr.63 Loss of ACI
Factory Setting: 00
Settings 00 Decelerate to 0 Hz
01 Stop immediately and display "EF"
| 02 Continue operation by last frequency command |
Pr.64 | User Defined Function for Display |
Factory Setting: 06
Settings 00 Displays AC drive output frequency (Hz)
01Display
02Output Voltage (E)
03DC Bus Voltage (u)
04PV (i)