Delta Electronics VFD-M manual Settings, Function, Description

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 73
Image 73
Manual background

Chapter 4 ParametersManual background

Settings

Function

 

 

 

 

 

 

 

 

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

Parameter value 18 programs Multi-Function Input Terminal:

 

 

M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)

 

 

to increase the AC drives internal counter. When an input is

 

 

received, the counter is increased by 1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trigger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mx counter value increase by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18 counter

 

1 when closed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

trigger signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

input.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Counter Trigger Signal

Note: The Counter Trigger input can be connected to an

external Pulse Signal Generator when counting a

 

 

 

 

process step or unit of material. See the diagram

 

 

below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indication value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Pr.64=1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Counter trigger signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multi-function input terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2ms

 

 

(Pr.38 to Pr.42 =18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Pr.97=3)

The trigger timing

 

 

Signal output with Pr.97

can't be less than

 

 

counter value is attained. (Pr.45/46=13)

2ms.(<250Hz)

 

 

Signal output with Pr.96

 

(Pr.96=5)

 

 

 

 

 

 

 

 

 

 

 

 

counter value is attained. (Pr.45/46=14)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter value 19 programs Multi-Function Input Terminal:

 

 

M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)

 

 

to reset the counter.

 

 

 

 

 

 

 

 

 

 

19

Counter Reset

 

Reset counter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mx "close": reset counter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19 reset the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

counter value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter value (20) to disable any Multi-Function Input Terminal:

 

 

M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)

20

No Function

Note: Purpose of this function is to isolate unused Multi-

Function Input Terminals. Any unused terminals should

 

 

 

 

be programmed to 20 to insure they have no effect on

 

 

drive operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-38

Revision May 2008, ME14, SW V3.04

Page 73
Image 73
Delta Electronics VFD-M manual Settings, Function, Description