Delta Electronics VFD-M manual Fault Name, Fault Descriptions

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 134
Image 134
Manual background

Chapter 6 Fault Code Information and MaintenanceManual background

Fault Name

 

Fault Descriptions

 

Corrective Actions

 

Over-current during steady state

1.

Check for possible poor insulation at the

 

operation:

 

 

output line.

 

1.

Short-circuit at motor output.

 

 

2.

Check for possible motor stall.

 

2.

Sudden increase in motor

 

3.

Replace with the AC drive with one that

 

 

loading.

 

 

 

has a higher output capacity (next HP

 

3.

AC drive output capacity is

 

 

 

size).

 

 

too small.

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Switch off power supply.

 

Internal memory IC can not be

2.

Check whether the input voltage falls

 

programmed.

 

within the rated AC drive input voltage.

 

 

 

3.

Switch the AC drive back on.

 

 

 

 

 

 

 

 

1.

Check the connections between the

 

Internal memory IC can not be

 

main control board and the power

 

read.

 

board.

 

 

 

2.

Reset drive to factory defaults.

 

The external terminal EF-GND

When external terminal EF-GND is closed,

 

the output will be turned off (under N.O.

 

goes from OFF to ON.

 

E.F.).

 

 

 

 

Auto accel/decel failure

Don’t use the function of auto acceleration/

 

deceleration.

 

 

 

 

Ground fault :

 

 

 

The AC drive output is abnormal.

Ground fault :

 

When the output terminal is

 

grounded (short circuit current is

1.

Check whether the IGBT power module

 

50% more than the AC drive rated

 

 

is damaged.

 

current), the AC drive power

 

 

2.

Check for possible poor insulation at

 

module may be damaged. The

 

 

the output line.

 

short circuit protection is provided

 

 

for AC drive protection, not user

 

 

 

protection.

 

 

 

Communication Error

1.

Check the connection between the AC

 

 

drive and computer for loose wires.

 

Please refer to Pr.92.

2.

Check if the communication protocol is

 

 

 

 

properly set.

 

 

 

1.

When the external input terminal (base-

 

External Base Block.

 

block) is active, the AC drive output will

 

 

be turned off.

 

AC drive output is turned off.

 

 

2.

Disable this connection and the AC

 

 

 

 

 

 

 

drive will begin to work again.

 

 

 

 

 

Revision May 2008, ME14, SW V3.04

6-3

Page 134
Image 134
Delta Electronics VFD-M manual Fault Name, Fault Descriptions