Appendix A SpecificationsInput

Voltage Class

Model Number VFD-XXXM

Max. Applicable Motor Output (kW)

Max. Applicable Motor Output (hp)

Rating

Rated Output Capacity (kVA)

 

 

Rated Output Current (A)

Output

Maximum Output Voltage (V)

Carrier Frequency (kHz)

 

Output Frequency (Hz)

Rating

Rated Input Current (A)

Rated Voltage, Frequency

Input

Voltage Tolerance

 

 

Frequency Tolerance

Cooling Method

Weight (kg)

Voltage Class

Model Number VFD-XXXM

Max. Applicable Motor Output (kW)

Max. Applicable Motor Output (hp)

Rating

Rated Output Capacity (kVA)

 

 

Rated Output Current (A)

Output

Maximum Output Voltage (V)

Carrier Frequency (kHz)

Rating

Output Frequency (Hz)

Rated Input Current (A)

 

Input

Rated Voltage, Frequency

Voltage Tolerance

 

 

Frequency Tolerance

Cooling Method

Weight (kg)

 

 

 

 

 

 

460V Class

 

 

007

015

 

022

 

037

 

055

075

0.75

1.5

 

2.2

 

3.7

 

5.5

7.5

1.0

2.0

 

3.0

 

5.0

 

7.5

10

2.3

3.1

 

3.8

 

6.2

 

9.9

13.7

3.0

4.0

 

5.0

 

8.2

 

13

18

 

 

 

3-phase

 

Proportional

 

to Input

Voltage

 

 

 

 

 

 

 

0.1~400 Hz

 

 

 

 

 

 

 

 

 

1-15

 

 

 

 

 

 

 

 

 

3-phase

 

 

4.2

5.7

 

6.0

 

8.5

 

14

23

 

 

 

3-phase 380-480 VAC, 50/60Hz

 

 

 

 

 

± 10% (342~528 VAC)

 

 

 

 

 

 

 

 

± 5% (47~63 Hz)

 

 

1.5

 

 

 

 

Fan Cooled

 

 

1.5

 

2.0

 

3.2

 

3.2

3.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575V Class

 

 

 

007

 

015

 

 

022

 

 

037

 

055

075

 

0.75

 

1.5

 

2.2

 

3.7

 

5.5

7.5

 

1.0

 

2.0

 

3.0

 

5.0

 

7.5

10

 

1.7

 

3.0

 

4.2

 

6.6

 

9.9

12.2

 

1.7

 

3.0

 

4.2

 

6.6

 

9.9

12.2

 

 

 

3-phase

Proportional

to Input

Voltage

 

 

 

 

 

 

 

0.1~400 Hz

 

 

 

 

 

 

 

 

 

1-10

 

 

 

 

 

 

 

 

 

3-phase

 

 

 

2.4

 

4.2

 

5.9

 

 

7.0

 

10.5

12.9

 

 

 

3-phase 500-600 VAC, 50/60Hz

 

 

 

 

 

-15% ~ +10% (425~660 V)

 

 

 

 

 

 

 

 

± 5% (47~63 Hz)

 

 

 

1.5

 

 

 

 

Fan Cooled

 

 

 

 

1.5

 

2.0

 

3.2

 

3.2

3.3

 

 

General Specifications

 

Control System

SPWM (Sinusoidal Pulse Width Modulation) control (V/F or

 

 

sensorless vector control)

 

Freq. Setting Resolution

0.1Hz

Characteristics

Output Frequency Resolution

0.1Hz

Torque Characteristics

Including the auto-torque, auto-slip compensation; starting torque

 

 

can be 150% at 5.0Hz

 

 

 

Overload Endurance

150% of rated current for 1 minute

 

Skip Frequency

Three zones, settings range 0.1-400Hz

 

Accel/Decel Time

0.1 to 600 seconds (4 Independent settings for Accel/Decel Time)

Control

Stall Prevention Level

Operation frequency 0-60Hz, output 0-100% rated current

 

Frequency Setting

20 to 200%, Setting of Rated Current

 

 

 

DC Injection Braking

Start time 0-5 seconds, stop time 0-25 seconds

 

 

 

Braking Torque

Approx. 20% (up to 125% possible with option brake resistor or

 

brake unit externally mounted, 1-15HP braking transistor built-in)

 

 

 

V/F Pattern

Adjustable V/F pattern

A-2

Revision May 2008, ME14, SW V3.04