Pr.105 | Control Mode |
Chapter 4 Parameters
Factory Setting: 00
Settings 00 | V/F Control |
01 | |
|
|
Pr.106 | Rated Slip |
| Settings 0.00 to 10.00 Hz |
Unit: 0.01Hz
Factory Setting: 3.0
Example of Slip calculation: The rated speed of 4 poles/3 φ/ 60Hz/ 220V on the nameplate is
1710RPM. The rated slip is then:
| Pr.107 | Vector Voltage Filter | Unit: 2ms | ||
|
| Settings | 5 to 9999 | Factory Setting: 10 | |
|
|
|
|
| |
| Pr.108 | Vector Slip Compensation Filter | Unit: 2ms | ||
|
| Settings | 25 to 9999 | Factory Setting: 50 | |
|
|
|
| ||
| This parameter sets the |
| |||
| Example: Pr. 107 = 10 X 2ms =20ms, Pr. 108 = 50 X 2 ms =100ms. |
| |||
|
|
|
|
| |
| Pr.109 | Selection for Zero Speed Control |
| ||
|
|
|
|
| Factory Setting: 00 |
|
| Settings | 00 No output |
| |
|
|
| 01 Control by DC voltage |
| |
|
|
| |||
| This parameter is used to select the control method at zero speed. If set to 01, the voltage in | ||||
| Pr.110 is used for holding torque. |
| |||
|
|
|
| ||
| Pr.110 | Voltage of Zero Speed Control | Unit: 0.1% | ||
|
| Settings | 0.0 to 20.0 % of Max. output voltage (Pr.05) | Factory Setting: 5.0 | |
|
|
|
|
|
|
This parameter should be used in conjunction with Pr.109.
Example: if Pr.05 = 100 and this parameter is set to 20.0, the level of output voltage is 100X20.0% = 20.
Pr.111 Deceleration S Curve
Settings 00 to 07Factory Setting: 00
When this parameter is set differently to zero, it selects a deceleration