Delta Electronics VFD-M manual Pr.105, Control Mode, Pr.106, Pr.107, Pr.108, Pr.109, Pr.110

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 110
Image 110
Pr.105

Pr.105

Control Mode

Chapter 4 ParametersControl Mode

Factory Setting: 00

Settings 00

V/F Control

01

Sensor-less Control

 

 

Pr.106

Rated Slip

 

Settings 0.00 to 10.00 Hz

Unit: 0.01Hz

Factory Setting: 3.0

Example of Slip calculation: The rated speed of 4 poles/3 φ/ 60Hz/ 220V on the nameplate is

1710RPM. The rated slip is then: 60-(1710/(120/P))=3Hz. (being P the number of poles)

 

Pr.107

Vector Voltage Filter

Unit: 2ms

 

 

Settings

5 to 9999

Factory Setting: 10

 

 

 

 

 

 

Pr.108

Vector Slip Compensation Filter

Unit: 2ms

 

 

Settings

25 to 9999

Factory Setting: 50

 

 

 

 

 

This parameter sets the low-pass filter in vector control.

 

 

Example: Pr. 107 = 10 X 2ms =20ms, Pr. 108 = 50 X 2 ms =100ms.

 

 

 

 

 

 

 

Pr.109

Selection for Zero Speed Control

 

 

 

 

 

 

Factory Setting: 00

 

 

Settings

00 No output

 

 

 

 

01 Control by DC voltage

 

 

 

 

 

This parameter is used to select the control method at zero speed. If set to 01, the voltage in

 

Pr.110 is used for holding torque.

 

 

 

 

 

 

Pr.110

Voltage of Zero Speed Control

Unit: 0.1%

 

 

Settings

0.0 to 20.0 % of Max. output voltage (Pr.05)

Factory Setting: 5.0

 

 

 

 

 

 

This parameter should be used in conjunction with Pr.109.

Example: if Pr.05 = 100 and this parameter is set to 20.0, the level of output voltage is 100X20.0% = 20.

Pr.111 Deceleration S Curve

Settings 00 to 07Factory Setting: 00

When this parameter is set differently to zero, it selects a deceleration S-curve and overrides Pr.14. Otherwise, Pr.14 sets the deceleration S-curve.

Revision May 2008, ME14, SW V3.04