Chapter 4 Parameters

Content

Address

Functions

Error code:

00:No errors occurred

01:Over-current (oc)

03:Overheat (oH)

04:Drive overload (oL)

05:Motor overload1 (oL1)

06:External fault (EF)

07:CPU failure (cF1)

Status monitor

 

08: CPU or analog circuit failure (cF3)

 

09: Hardware protection failure (HPF)

Read only

 

2100H

10: Current exceeds 2 times rated current during accel (ocA)

 

 

11: Current exceeds 2 times rated current during decel (ocd)

 

 

 

 

12: Current exceeds 2 times rated current during steady state

 

 

operation (ocn)

 

 

13: Ground Fault (GF)

 

 

14: Low voltage (Lv)

 

 

15: Reserved

 

 

16: CPU failure 1 (cF2)

 

 

17: Base block

 

 

18: Overload (oL2)

 

 

19: Auto accel/decel failure (cFA)

 

 

20: Software protection enable (codE)

 

 

 

Status of AC Drive

 

 

 

00: RUN LED light off, STOP LED light up

 

 

Bit 0-1

01: RUN LED blink, STOP LED light up

 

 

10: RUN LED light up, STOP LED blink

 

 

 

 

2101H

 

11: RUN LED light up, STOP LED light off

 

Bit 2

01: Jog active

 

 

 

 

 

00: REV LED light off, FWD LED light up

 

 

Bit 3-4

01: REV LED blink, FWD LED light up

 

 

10: REV LED light up, FWD LED blink

 

 

 

 

 

 

11: REV LED light up, FWD LED light off

 

 

Bit 5-7

Reserved

 

 

Bit 8

1: Main freq. Controlled by communication

 

 

Bit 9

1: Main freq. Controlled by external terminal

 

 

Bit 10

1: Operation command controlled by

 

 

communication

 

 

 

 

 

Bit 11

1: Parameters have been locked

 

 

Bit 12

0: Stop 1: Run

 

 

 

 

 

 

Bit 13

1: Jog command

 

 

Bit 14-15

Reserved

 

2102H Frequency command F (XXX.XX)

 

2103H Output Frequency H (XXX.XX)

 

2104H Output Current A (XXX.X)

 

2105H DC-BUS Voltage U (XXX.X)

Revision May 2008, ME14, SW V3.04

4-69

Page 104
Image 104
Delta Electronics VFD-M manual CPU or analog circuit failure cF3