Chapter 4 ParametersManual background

When Line Start Lockout is disabled (also known as Auto-Start), the drive will start when powered-up with run commands applied. To start in Line Start Lockout mode, the AC drive must see the run command go from stop to run after power up. When enabled, the AC drive will not start when powered up if run commands were applied.

Pr. 147 Decimal Number of Accel / Decel Time

 

Factory Setting: 00

Settings 00

One Decimal

01

Two Decimals

It sets the number of decimals in the accel/decel time. It can be used for Acceleration / Deceleration Time 1, Acceleration / Deceleration Time 2 and JOG Acceleration / Deceleration Time.

 

Pr. 148

Number of Motor Poles

 

 

 

Settings

02 to 20

Factory Setting: 04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr. 149

Gear Ratio for Simple Index Function

 

 

 

Settings

4 to 1000

Factory Setting: 200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr. 150

Index Angle for Simple Index Function

 

 

 

Settings

00.0 to 360.0

Factory Setting: 180.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr. 151

Deceleration Time for Simple Index Function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 0.00

 

 

Settings

0.00 to 100.00 sec

 

 

 

 

0.00 Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This parameter should be used with Pr. 39-Pr.42 (setting 31).

 

 