Chapter 4 Parameters

Command code: 10H, write multiple data to registers

For example, set the multi-step speed,

Pr.17=50.00 (1388H), Pr.18=40.00 (0FA0H). AC drive address is 01H.

ASCII Mode:

Command message:

STX

‘:’

 

 

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘1’

CMD 0

‘0’

 

‘0’

Starting data address

‘0’

 

‘1’

 

 

‘1’

 

‘0’

Number of data

‘0’

(count by word)

‘0’

 

‘2’

Number of data

‘0’

count by byte

‘4’

 

 

‘1’

The first data content

‘3’

 

‘8’

 

 

‘8’

 

‘0’

The second data content

‘F’

 

‘A’

 

 

‘0’

LRC Check

‘8’

‘E’

 

END

CR

LF

 

 

 

Response message:

STX

‘:’

 

 

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘1’

CMD 0

‘0’

 

‘0’

Starting data address

‘0’

 

‘1’

 

 

‘1’

 

‘0’

Number of data

‘0’

(count by word)

‘0’

 

‘2’

LRC Check

‘D’

‘C’

 

END

CR

LF

 

 

 

Revision May 2008, ME14, SW V3.04

4-65

Page 100
Image 100
Delta Electronics VFD-M manual Starting data address ‘0’ ‘1’