Chapter 4 Parameters

 

 

 

Parameter

Explanation

Settings

Factory

Customer

 

 

Setting

 

 

Pr.59

Electronic Thermal

30 to 300 sec

60

 

 

 

Motor Overload

 

 

 

 

 

 

 

 

 

 

 

00: Over-Torque Detection Disable

 

 

 

 

 

 

01: Enabled during constant speed operation

 

 

 

 

 

 

until the allowable time for detection

 

 

 

 

 

 

(Pr.62) elapses.

 

 

 

 

 

Over-Torque

02: Enabled during constant speed operation

00

 

 

 

Pr.60

and halted after detection.

 

 

 

Detection Mode

 

 

 

 

03: Enabled during acceleration until the

 

 

 

 

 

 

 

 

 

 

 

 

allowable time for detection (Pr.62)

 

 

 

 

 

 

elapses.

 

 

 

 

 

 

04: Enabled during acceleration and halted

 

 

 

 

 

 

after detection.

 

 

 

 

 

 

 

 

 

 

 

Pr.61

Over-Torque

30 to 200 %

150

 

 

 

Detection Level

 

 

 

 

 

 

 

 

 

Pr.62

Over-Torque

0.0 to 10.0 seconds

0.1

 

 

 

Detection Time

 

 

 

 

 

 

 

 

 

 

 

00: Decelerate to 0 Hz

 

 

 

 

Pr.63

Loss of ACI

01: Stop immediately and display "EF"

00

 

 

 

(4-20mA)

02: Continue operation by last frequency

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

00: Display AC drive output Frequency (Hz)

 

 

 

 

 

 

01: Display User-defined output Frequency

 

 

 

 

 

 

(H*Pr.65)

 

 

 

 

 

 

02: Output Voltage (E)

 

 

 

 

 

 

03: DC Bus Voltage (u)

 

 

 

 

 

User Defined Function

04: PV (i)

 

 

 

 

Pr.64

05: Display the value of internal counter (c)

06

 

 

 

 

for Display

06: Display the setting frequency (F or o=%)

 

 

 

 

 

 

 

 

 

 

 

 

07: Display the parameter setting (Pr.00)

 

 

 

 

 

 

08: Reserved

 

 

 

 

 

 

09: Output Current (A)

 

 

 

 

 

 

10: Display program operation (0.xxx), Fwd,

 

 

 

 

 

 

or Rev

 

 

 

 

 

 

 

 

 

 

 

Pr.65

Coefficient K

0.01 to 160.0

1.00

 

 

 

 

 

 

 

 

 

 

Pr.66

Communication

0.00 to 400.0 Hz

0.00

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

Pr.67

Skip Frequency 1

0.00 to 400.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

Pr.68

Skip Frequency 2

0.00 to 400.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

Pr.69

Skip Frequency 3

0.00 to 400.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

Pr.70

Skip Frequency Band

0.00 to 20.00 Hz

0.00

 

 

 

 

 

 

 

 

 

Revision May 2008, ME14, SW V3.04

4-7

Page 42
Image 42