Delta Electronics VFD-M manual Motor Spec. 60Hz, Motor Spec. 50Hz, Pr.10, Pr.11, Pr.12, Pr.13

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 59
Image 59
Motor Spec. 60Hz

Chapter 4 ParametersMotor Spec. 50Hz

 

(2) Fans and Pumps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Spec. 60Hz

 

Factory Settings

 

Motor Spec. 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

No.

 

Set value

 

V

 

 

 

 

 

 

 

 

No.

 

 

Set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220

 

 

 

 

 

 

 

 

 

 

 

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.03

 

60.0

 

 

 

 

 

 

 

 

 

 

 

Pr.03

 

 

50.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.04

 

60.0

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.04

 

 

50.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.05

 

220.0

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.05

 

 

220.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.06

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.06

 

 

25

 

 

 

50

 

 

 

 

 

 

 

 

 

 

Pr.07

 

50.0

 

50

 

 

 

 

 

 

 

 

 

 

Pr.07

 

 

50.0

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.08

 

1.5

 

 

 

 

 

 

 

 

 

 

 

Pr.08

 

 

1.3

 

 

 

10

 

 

 

 

 

 

 

 

 

 

Pr.09

 

10.0

 

10

 

 

 

 

 

 

 

 

 

 

Pr.09

 

 

10.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

30

60.0f

 

 

 

 

 

 

 

 

 

1.3

25

50.0f

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) High Starting Torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Spec. 60Hz

 

Factory Settings

 

Motor Spec. 50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

No.

 

 

Set value

 

V

 

 

 

 

 

 

 

 

No.

 

Set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220

 

 

 

 

 

 

 

 

 

 

 

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.03

 

 

60.0

 

 

 

 

 

 

 

 

 

 

 

Pr.03

 

50.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.04

 

 

60.0

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.04

 

50.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.05

 

 

220.0

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.05

 

220.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.06

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.06

 

2.2

 

 

 

23

 

 

 

 

 

 

 

 

 

Pr.07

 

 

23.0

 

23

 

 

 

 

 

 

 

 

 

 

Pr.07

 

23.0

 

 

 

 

 

 

 

 

 

 

 

 

Pr.08

 

 

1.5

 

 

 

 

 

 

 

 

 

 

 

Pr.08

 

1.3

 

 

 

18

 

 

 

 

 

 

 

 

 

 

Pr.09

 

18.0

 

14

 

 

 

 

 

 

 

 

 

 

Pr.09

 

14.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

3

 

60.0f

 

 

 

 

 

 

 

 

1.3 2.2

60.0f

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.10

 

 

 

 

Acceleration Time 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit:

 

0.1 or 0.01 sec

 

Pr.11

 

Deceleration Time 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit:

 

0.1 or 0.01 sec

 

Pr.12

 

 

 

 

Acceleration Time 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit:

 

0.1 or 0.01 sec

 

Pr.13

 

Deceleration Time 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit:

 

0.1 or 0.01 sec

 

 

Settings

0.1 to 600.0 sec or 0.01 to 600.0 sec

 

 

 

 

 

 

 

 

Factory Setting: 10.0

Pr.10. This parameter is used to determine the time required for the AC drive to ramp from 0 Hz to its Maximum Output Frequency (Pr.03). The rate is linear unless the S-Curve (Pr.14) is “Enabled”.

Pr.11. This parameter is used to determine the time required for the AC drive to decelerate from the Maximum Output Frequency (Pr.03) down to 0 Hz. The rate is linear unless the S- Curve (Pr.14) is “Enabled”.

Pr.12 and Pr.13: Provide an additional Accel/Decel time although Time 1 is the default. A Multi-Function input terminal must be programmed to select Accel/ or Decel/ Time 2 and the terminal must be closed to select Accel/Decel Time 2 (See Pr.38 to Pr.42).

In the below diagram, suppose the Maximum Output Frequency is 60 Hz (Master Freq), Minimum Output Frequency (start-up) is 1.0 Hz, and accel/decel time 1 is 10 seconds. The actual time for the AC drive to accelerate from start-up to 60 Hz is 9.83 seconds (deceleration time is also 9.83 seconds), can be determined by the formula.

4-24

Revision May 2008, ME14, SW V3.04