Chapter 4 Parameters
05Displays the value of the internal counter (c)
06Displays the setting Frequency (F)
07Displays the parameter setting (P)
08Reserved
09Output Current (A)
10Display program operation (0. xxx), Fwd, or Rev
The parameter can be set to display the
Pr.65 | Coefficient K | |
| Settings | 0.01 to 160.0 |
Unit: 0.01
Factory Setting: 1.00
The coefficient K determines the multiplying factor for the
The display value is calculated as follows:
Display value = output frequency x K
The display window is only capable of showing four digits, yet you could use Pr.65 to create
larger numbers. The display windows uses decimal points to signify numbers up to three digits
as illustrated in next page:
Display | Number Represented | |
9999 | The absence of a decimal point indicates a | |
|
| |
999.9 | A signal decimal point between the middle and the | |
decimal point. For example, the number 123.4 would be displayed as “123.4”. | ||
| ||
|
| |
| A single decimal point after the | |
9999. | it indicates that a zero follows the | |
| would be displayed as “1234.” | |
|
| |
| Two decimal points (one between the middle and the | |
999.9. | after the | |
zeros follow the | ||
| ||
| displayed as “345.6.”. | |
|
|
Pr.66 | Communication Frequency |
| Settings 0.00 to 400.0 Hz |
Unit: 0.1 Hz
Factory Setting: 0.00
This parameter defines the Master Frequency when the AC drive is controlled by the
communication interface.
Revision May 2008, ME14, SW V3.04 |