Chapter 4 Parameters

 

Settings

Function

 

 

 

 

 

 

 

 

 

 

 

 

Description

14

Increase Master

Parameter values 14, 15 program the Multi-Function Input

Frequency

Terminals: M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or

 

 

 

 

 

M5 (Pr.42) to incrementally increase/ decrease the Master

 

 

 

 

 

 

Frequency each time an input is received.

 

 

Decrease Master

 

 

 

 

 

UP

 

 

 

Mx "Close": Freq. will increase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

setting by 14

 

 

Frequency

 

 

 

 

 

by one unit.

 

 

 

 

 

 

DOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mx "Open":Freq. will decrease

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting by 15

 

 

 

 

 

 

 

 

 

 

 

by one unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

Run PLC Program

Parameter value 16 programs Multi-Function Input Terminal:

 

 

 

M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42)

 

 

 

 

 

 

to enable the AC drive internal PLC program. Parameter

 

 

 

value 17 programs an input terminal to pause the PLC

 

 

 

program.

 

 

 

 

 

 

 

 

 

 

 

 

PLC operation

 

Mx "Close": Run PLC.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting by 16

 

 

 

 

 

 

 

 

 

 

 

 

17

Pause PLC Program

 

 

 

 

 

 

 

 

 

 

Mx "Open":Pause PLC.

 

 

 

 

 

 

 

 

 

 

 

setting by 17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Pr.17 to Pr.23, Pr.78, Pr. 79, Pr.81 to Pr.87 define the

 

 

 

 

 

PLC program. Another related function is “30 One-Shot

 

 

 

 

 

PLC Run”. It can be set to use a not-latched contact as

 

 

 

 

 

the run signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision May 2008, ME14, SW V3.04

4-37