Chapter 4 Parameters
Note: From the diagram shown below, the original setting accel/decel time will be for reference
when the function of the
based on the
Pr.112 | External Terminal Scanning Time |
| Settings 01 to 20 |
Unit: 2msec
Factory Setting: 01
This function screens the signal on I/O terminals for CPU malfunctions due to external
transients. A setting of 02, makes the scanning time to be 2 x 2 = 4 msec.
Set Pr.77 to 02 before changing settings in Pr.112.
Pr.113 | Restart Method after Fault (oc, ov, BB) |
Factory Setting: 01
Settings 00 None speed search
01Continue operation after fault speed search from speed reference
02Continue operation after fault speed search from Minimum speed
This parameter is used to select the restart method after certain faults.
Pr. 114 | Cooling Fan Control |
Factory Setting: 02
Settings 00 Fan Off when the drive stop after 1 Min
01AC Drive Runs and Fan On, AC Drive Stops and Fan Off
02Always Run
03Reserved
Pr. 115 | PID Set Point Selection |
Factory Setting: 00
Settings 00 Disable
01Keypad (based on Pr.00 setting)
02AVI (external
03ACI (external
04PID set point (Pr.125)
Revision May 2008, ME14, SW V3.04 |