Chapter 4 Parameters
RTU mode:
START | A silent interval of more than 10 ms |
|
|
ADR | Communication address: |
|
|
CMD | Command code: |
|
|
DATA |
|
| Contents of data: |
……. | |
|
|
DATA 0 |
|
|
|
CRC CHK Low | CRC check sum: |
CRC CHK High | |
|
|
END | A silent interval of more than 10 ms |
|
|
3.3ADR (Communication Address)
Valid communication addresses are in the range of 0 to 254. An address equals to 0 means a broadcast to all AC drives (AMD) in the network. In this case, the AMD will not reply to the master device.
For example, communication to AMD with address 16 decimal: ASCII mode: (ADR 1, ADR 0)=’1’,’0’ => ‘1’=31H, ‘0’=30H RTU mode: (ADR)=10H
3.4Function (Function code) and DATA (data characters)
The format of data characters depends on the function code. The available function codes are described as follows:
03H: read data from register
06H: write single data to register
10H: write multiple data to registers
Revision May 2008, ME14, SW V3.04 |