Delta Electronics VFD-M manual Pr.47, Desired Freq. Attained & Preset Freq. Attained, Pr.48, Pr.49

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 78
Image 78
Pr.47

 

 

Chapter 4 Parameters

Pr.47

Desired Frequency Attained

Unit: 0.1Hz

 

Settings 0.00 to 400.0 Hz

Factory Setting: 0.00

This parameter allows monitoring a certain frequency and then activates one of the Multi-

function output terminals (Pr.45 or Pr.46 set to 8) when that frequency is achieved.

 

Freq.

 

Max. Output Detection range

Detection

range

Freq.

+

 

+4Hz

 

 

-2Hz

-

Desired Freq.

Pr.47

Preset Freq. Attained Indication Pr.45 to OFF Pr.46

Detection

range

-2Hz

Time

ON

OFF

Desired Freq.

Attained OFF

Indication

Pr.45 & Pr.46

ON

OFF

Desired Freq. Attained & Preset Freq. Attained

Pr.48

Adjust Bias of External Input Frequency

 

Settings 0.00 to 200.0%

Unit: 0.1Hz

Factory Setting: 0.00 Hz

This parameter provides a frequency offset when the source of frequency command is the

analog input.

 

Pr.49

Potentiometer Bias Polarity

 

 

 

Factory Setting: 00

 

 

Settings 00

Positive Bias

 

 

01

Negative Bias

 

 

 

 

This parameter sets the potentiometer Bias Frequency to be positive or negative.

 

Pr.50

Potentiometer Frequency Gain

Unit: 1%

 

 

Settings 0.10 to 200.0%

Factory Setting: 100.0

 

 

 

 

This parameter sets the ratio of analog input vs frequency output.

Pr.51

Potentiometer Reverse Motion Enable

Factory Setting: 00

Settings 00 Reverse Motion Disabled in negative bias 01 Reverse Motion Enabled in negative bias

Revision May 2008, ME14, SW V3.04