| Chapter 4 Parameters |
Pr.47 | Desired Frequency Attained | Unit: 0.1Hz |
| Settings 0.00 to 400.0 Hz | Factory Setting: 0.00 |
This parameter allows monitoring a certain frequency and then activates one of the Multi-
function output terminals (Pr.45 or Pr.46 set to 8) when that frequency is achieved.
| Freq. |
| |
Max. Output Detection range | Detection | ||
range | |||
Freq. | + |
| +4Hz |
| |||
| |||
- |
Desired Freq.
Pr.47
Preset Freq. Attained Indication Pr.45 to OFF Pr.46
Detection |
range |
Time |
ON | OFF |
Desired Freq.
Attained OFF
Indication
Pr.45 & Pr.46
ON | OFF |
Desired Freq. Attained & Preset Freq. Attained
Pr.48 | Adjust Bias of External Input Frequency |
| Settings 0.00 to 200.0% |
Unit: 0.1Hz
Factory Setting: 0.00 Hz
This parameter provides a frequency offset when the source of frequency command is the
analog input.
| Pr.49 | Potentiometer Bias Polarity | |
|
|
| Factory Setting: 00 |
|
| Settings 00 | Positive Bias |
|
| 01 | Negative Bias |
|
|
|
|
This parameter sets the potentiometer Bias Frequency to be positive or negative.
| Pr.50 | Potentiometer Frequency Gain | Unit: 1% |
|
| Settings 0.10 to 200.0% | Factory Setting: 100.0 |
|
|
|
|
This parameter sets the ratio of analog input vs frequency output.
Pr.51 | Potentiometer Reverse Motion Enable |
Factory Setting: 00
Settings 00 Reverse Motion Disabled in negative bias 01 Reverse Motion Enabled in negative bias
Revision May 2008, ME14, SW V3.04 |