Pr.67

 

 

 

Chapter 4 Parameters

 

Pr.67

Skip Frequency 1

Unit: 0.1 Hz

 

Pr.68

Skip Frequency 2

Unit: 0.1 Hz

 

Pr.69

Skip Frequency 3

Unit: 0.1 Hz

 

 

Settings 0.00 to 400.0 Hz

Factory Setting: 0.00

These three parameters determine the three Skip Frequencies that in conjunction with Pr.70, Skip Frequency Band, will cause the AC drive to skip operating in each frequency band. Note: Pr.67 > Pr.68 > Pr.69.

 

Pr.70

Skip Frequency Band

Unit: 0.1 Hz

 

 

Settings 0.00 to 20.00 Hz

Factory Setting: 0.00

 

 

 

 

This parameter determines the frequency band for a given Skip Frequency. Half of the Skip Frequency Band is above the Skip Frequency and the other half is below. Programming this parameter to 0.1 disables all skip frequencies.

output freq.

Pr.67

 

 

 

Pr.68

 

 

Adjustable

 

 

 

 

 

 

range

 

 

 

Pr.69

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

Speed command

 

 

 

 

 

 

 

 

 

 

 

 

freqency

 

 

Decelerating

 

 

 

 

Pr.70

 

 

 

 

 

 

 

 

skip freq.

 

 

 

 

 

 

set point

 

 

 

 

Freq. to

 

 

 

 

 

 

 

 

be jumped

 

 

 

 

Accelerating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.71

PWM Carrier Frequency

 

 

 

 

 

 

 

 

Settings 115V series

 

 

 

 

 

 

Factory Setting: 15

 

 

230V series

01 to 15 (1KHz to 15KHz)

 

 

 

 

VFD075M43A is 10

 

 

460V series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575V series

01 to 10 (1KHz to 10KHz)

 

Factory Setting: 6

Note: 1-9kHz in sensorless vector control mode

The parameter defines the carrier frequency of the PWM (Pulse-Width Modulated) output.