| Chapter 4 Parameters |
| |
| Pr. 119 | Differential Time (D) | Unit: 0.01sec |
|
| Settings 0.00 to 1.00 sec | Factory Setting: 0.00 |
|
|
|
|
This parameter determines the damping effect for the PID feedback loop. If the differential time is long, any oscillation will quickly subside. If the differential time is short, the oscillation will subside slowly.
Pr. 120 Integration’s Upper Bound Frequency |
|
Settings 00 to 100 % | Factory Setting: 100 % |
This parameter determines the integration’s upper frequency limit while operating in the PID feedback loop. (Limit = Pr.03×Pr.120). During a fast Integration response, it is possible for the frequency to surpass a reasonable point. This parameter will help limit this frequency spike.
Pr. 121 |
Unit: 0.1sec Factory Setting: 0.0
Settings 0.0 to 2.5 sec 0.0 disable
PI Control: When controlled by P action only, deviations cannot be eliminated entirely. To eliminate residual deviations, the P + I control is generally utilized. If PI is used, it could eliminate the deviation caused by
PD Control: when a deviation occurs, the system immediately generates some operational load that is greater than the single load generated by the
PID Control: Uses the