Parameter

Explanation

Settings

Factory

Customer

 

 

Setting

 

 

Pr.125

Source of PID Set

0.00 to 400.0Hz

0.00

 

 

 

Point

 

 

 

 

 

 

 

 

 

Pr.126

PID Offset Level

1.0 to 50.0 %

10.0

 

 

 

 

 

 

 

 

 

 

Pr.127

Detection Time of PID

0.1 to 300.0 sec

5.0

 

 

 

 

Offset

 

 

 

 

 

Pr.128

Minimum Reference

0.0 to 10.0 V

0.0

 

 

 

Value

 

 

 

 

 

 

 

 

 

Pr.129

Maximum Reference

0.0 to 10.0 V

10.0

 

 

 

Value

 

 

 

 

 

 

 

 

 

Pr.130

Invert Reference

00: Not inverted

00

 

 

 

 

 

 

 

Signal AVI (0-10V)

01: Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.131

Minimum Reference

0.0 to 20.0mA

4.0

 

 

 

Value (4-20mA)

 

 

 

 

 

 

 

 

 

Pr.132

Maximum Reference

0.0 to 20.0mA

20.0

 

 

 

Value (4-20mA)

 

 

 

 

 

 

 

 

 

Pr.133

Invert Reference

00: Not inverted

00

 

 

 

Signal (4-20mA)

01: Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.134

Analog Input Delay

00 to 9999 (per 2ms)

50

 

 

 

Filter for Set Point

 

 

 

 

 

 

 

 

 

 

Analog Input Delay

00 to 9999 (per 2ms)

 

 

 

 

Pr.135

Filter for Feedback

5

 

 

 

 

 

 

 

 

Signal

 

 

 

 

 

Pr.136

Sleep Period

0.0 to 6550.0 sec

0.0

 

 

 

 

 

 

 

 

 

 

Pr.137

Sleep Frequency

0.00 to 400.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

Pr.138

Wake Up Frequency

0.00 to 400.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

Pr.139

Treatment for Counter

00: Continue operation

00

 

 

 

Attained

01: Stop Immediately and display E.F.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Up/Down

00: Fixed Mode (keypad)

 

 

 

 

Pr.140

01: By Accel or Decel Time

00

 

 

 

Selection

02: Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.141

Save Frequency Set

00: Not Save

01

 

 

 

Point

01: Save

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00: Keypad Up/Down

 

 

 

 

Pr.142

Second Source of

01: AVI (0-10V)

 

 

 

 

02: ACI (4-20mA)

00

 

 

 

Frequency Command

 

 

 

 

 

03: Communication

 

 

 

 

 

 

04: Keypad potentiometer

 

 

 

 

 

 

 

 

 

 

 

 

 

115V/230V: 370-450 Vdc

380.0

 

 

 

Pr.143

Software Braking

 

 

 

 

 

460V: 740-900 Vdc

760.0

 

 

 

Level

 

 

 

 

 

 

 

 

 

 

 

575V: 925-1075 Vdc

950.0

 

 

 

 

 

 

 

 

 

 

Pr.144

Total operation time

Read Only

 

 

 

 

(Day)

 

 

 

 

 

 

 

 

 

4-12