| Chapter 4 Parameters |
|
| |
| Parameter | Explanation | Settings | Factory | Customer |
|
| Setting |
| ||||
|
|
| 00: Disable PLC operation |
|
|
|
|
|
| 01: Execute one program cycle |
|
|
|
| Pr.78 | PLC Operation Mode | 02: Continuously execute program cycles | 00 |
|
|
| 03: Execute one program cycle step by step |
|
| |||
|
|
|
|
|
| |
|
|
| 04: Continuously execute one program cycle |
|
|
|
|
|
| step by step |
|
|
|
|
|
|
|
|
|
|
| Pr.79 | PLC FWD/REV | 00 to 127 | 00 |
|
|
| Motion |
|
| |||
|
|
|
|
|
| |
| Pr.80 | Identity Code of the | Read only | ## |
|
|
| AC Motor Drive |
|
| |||
|
|
|
|
|
| |
| Pr.81 | Time Duration of 1st | 00 to 9999 sec | 00 |
|
|
| Step Speed |
|
| |||
|
|
|
|
|
| |
| Pr.82 | Time Duration of 2nd | 00 to 9999 sec | 00 |
|
|
| Step Speed |
|
| |||
|
|
|
|
|
| |
| Pr.83 | Time Duration of 3rd | 00 to 9999 sec | 00 |
|
|
| Step Speed |
|
| |||
|
|
|
|
|
| |
| Pr.84 | Time Duration of 4th | 00 to 9999 sec | 00 |
|
|
| Step Speed |
|
| |||
|
|
|
|
|
| |
| Pr.85 | Time Duration of 5th | 00 to 9999 sec | 00 |
|
|
| Step Speed |
|
| |||
|
|
|
|
|
| |
| Pr.86 | Time Duration of 6th | 00 to 9999 sec | 00 |
|
|
| Step Speed |
|
| |||
|
|
|
|
|
| |
| Pr.87 | Time Duration of 7th | 00 to 9999 sec | 00 |
|
|
| Step Speed |
|
| |||
|
|
|
|
|
| |
| Pr.88 | Communication | 01 to 254 | 01 |
|
|
| Address |
|
| |||
|
|
|
|
|
| |
|
|
| 00: 4800 bps |
|
|
|
| Pr.89 | Transmission Speed | 01: 9600 bps | 01 |
|
|
| 02: 19200 bps |
|
| |||
|
|
|
|
|
| |
|
|
| 03: 38400 bps |
|
|
|
|
|
|
|
|
|
|
|
|
| 00: Warn and Continue Operating |
|
|
|
| Pr.90 | Transmission Fault | 01: Warn and RAMP to Stop | 03 |
|
|
| Treatment | 02: Warn and COAST to Stop |
|
| ||
|
|
|
|
| ||
|
|
| 03: Keep Operation without Warning |
|
|
|
|
|
|
|
|
|
|
| Pr.91 | Time Out Detection | 0.0: Disable | 0.0 |
|
|
| 0.1 to 120.0 sec |
|
| |||
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| 00: MODBUS ASCII mode, <7,N,2> |
|
|
|
|
|
| 01: MODBUS ASCII mode, <7,E,1> |
|
|
|
| Pr.92 | Communication | 02: MODBUS ASCII mode, <7,O,1> | 00 |
|
|
| Protocol | 03: MODBUS RTU mode, <8,N,2> |
|
| ||
|
|
|
|
| ||
|
|
| 04: MODBUS RTU mode, <8,E,1> |
|
|
|
|
|
| 05: MODBUS RTU mode, <8,O,1> |
|
|
|
|
|
|
|
|
|
|
Revision May 2008, ME14, SW V3.04 |