Chapter 4 Parameters

Pr. 152

Skip Frequency Width

 

Settings

0.00 to 400.00Hz

Pr. 153

Bias Frequency Width

 

Settings

0.00 to 400.00Hz

Factory Setting: 0.00

Factory Setting: 0.00

Frequency of Δ top point Fup= master frequency F + Pr.152 + Pr.153. Frequency of Δ down point Fdown= master frequency F – Pr.152 – Pr.153.

Pr.152

Master Pr.10, 12 Frequency

(F)

Pr.11, 13

Fup

Double Pr. 153

Fdown

Pr. 154

Reserved

Pr.155

Compensation Coefficient for Motor Instability

Factory Setting: 0.0

Settings 0.1 to 5.0 (recommended setting 2.0) 0.0 Disable

This parameter is used to improve a condition of unstable current in any specific area. For higher frequencies, you can adjust this parameter to 0.0, and increase the setting value in Pr.155 for 30HP and above (a setting of 2.0 is recommended).

 

Pr.156

Communication Response Delay Time

 

 

 

Settings 0 to 200 (x500µs)

Factory Setting: 0

 

 

 

 

This parameter is used to set communication response delay time. If you set Pr. 156 to 1 the communication response delay time will be 1 X 500µs=500µs, set Pr. 156 to 2 the communication response delay time will be 2 X 500µs=1000µs.

Pr.157

Communication Mode Selection

Factory Setting: 1

Settings 0

Delta ASCII

1

MODBUS

 

 

4-84

Revision May 2008, ME14, SW V3.04

Page 119