Chapter 4 Parameters | ||
Pr. 152 | Skip Frequency Width | |
| Settings | 0.00 to 400.00Hz |
Pr. 153 | Bias Frequency Width | |
| Settings | 0.00 to 400.00Hz |
Factory Setting: 0.00
Factory Setting: 0.00
Frequency of Δ top point Fup= master frequency F + Pr.152 + Pr.153. Frequency of Δ down point Fdown= master frequency F – Pr.152 – Pr.153.
Pr.152
Master Pr.10, 12 Frequency
(F)
Pr.11, 13
Fup
Double Pr. 153
Fdown
Pr. 154 | Reserved |
Pr.155 | Compensation Coefficient for Motor Instability |
Factory Setting: 0.0
Settings 0.1 to 5.0 (recommended setting 2.0) 0.0 Disable
This parameter is used to improve a condition of unstable current in any specific area. For higher frequencies, you can adjust this parameter to 0.0, and increase the setting value in Pr.155 for 30HP and above (a setting of 2.0 is recommended).
| Pr.156 | Communication Response Delay Time |
|
|
| Settings 0 to 200 (x500µs) | Factory Setting: 0 |
|
|
|
|
This parameter is used to set communication response delay time. If you set Pr. 156 to 1 the communication response delay time will be 1 X 500µs=500µs, set Pr. 156 to 2 the communication response delay time will be 2 X 500µs=1000µs.
Pr.157 | Communication Mode Selection |
Factory Setting: 1
Settings 0 | Delta ASCII |
1 | MODBUS |
|
|
Revision May 2008, ME14, SW V3.04 |