Delta Electronics VFD-M manual Pr.80, Pr.81, Pr.82, Pr.83, Pr.84, Pr.85, Pr.86, Pr.87, Pr.88

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 93
Image 93
Pr.80

Chapter 4 Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.80

Identity Code of the AC Motor Drive

 

 

 

 

 

 

 

 

 

 

 

 

Settings Read Only

 

 

 

 

 

 

 

 

Factory Setting: ##

 

 

 

 

 

 

 

 

 

 

 

 

 

This parameter displays the identity code of the AC motor drive. The capacity, rated current,

 

rated voltage and the max. carrier frequency relate to the identity code. Users can use the

 

 

following table to check how the rated current, rated voltage and max. carrier frequency of the

 

AC motor drive correspond to the identity code.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115V series

 

 

 

230V series

 

 

 

 

 

kW

0.2

0.4

0.75

0.4

 

0.75

1.5

2.2

3.7

 

5.5

 

 

HP

0.25

0.5

1.0

0.5

 

1

2

3

5

 

7.5

 

Model Number (Pr.80)

20

22

24

00

 

02

04

06

08

 

10

 

Rated Output Current (A)

1.6

2.5

4.2

2.5

 

5.0

7.0

10

17

 

25

 

Max. Carrier Frequency (kHz)

 

 

 

 

15kHz

 

 

 

 

 

 

 

 

 

 

460V series

 

 

kW

0.75

1.5

 

2.2

3.7

 

5.5

7.5

HP

1

2

 

3

5

 

7.5

10

Model Number (Pr.80)

03

05

 

07

09

 

11

13

Rated Output Current (A)

3.0

4.0

 

5.0

8.2

 

13

18

Max. Carrier Frequency (kHz)

 

 

 

15kHz

 

 

575V series

0.75

1.5

2.2

3.7

5.5

7.5

1

2

3

5

7.5

10

50

51

52

53

54

55

1.7

3.0

4.2

6.6

9.9

12.2

 

 

10kHz

 

 

 

Pr.81

Time Duration of 1st Step Speed (correspond to Pr.17)

Unit: 1 sec

 

Pr.82

Time Duration of 2nd Step Speed (correspond to Pr.18)

Unit: 1 sec

 

Pr.83

Time Duration of 3rd Step Speed (correspond to Pr.19)

Unit: 1 sec

 

Pr.84

Time Duration of 4th Step Speed (correspond to Pr.20)

Unit: 1 sec

 

Pr.85

Time Duration of 5th Step Speed (correspond to Pr.21)

Unit: 1 sec

 

Pr.86

Time Duration of 6th Step Speed (correspond to Pr.22)

Unit: 1 sec

 

Pr.87

Time Duration of 7th Step Speed (correspond to Pr.23)

Unit: 1 sec

Settings 00 to 9999 secondFactory Setting: 00

Pr.81 to Pr.87 input the duration of each Multi-step speed operation defined by Pr.17 to Pr.23. Note: If any duration is set to “0” (sec), the corresponding step operation will be skipped. This is

commonly used to reduce the number of program steps.

Pr.88

Communication Address

 

 

Settings 01 to 254

Factory Setting: 01

4-58

Revision May 2008, ME14, SW V3.04

Page 93
Image 93
Delta Electronics VFD-M manual Pr.80, Pr.81, Pr.82, Pr.83, Pr.84, Pr.85, Pr.86, Pr.87, Pr.88