External Up/Down Selection

Chapter 4 ParametersManual background

These two parameters are used to set the analog input delay filter in set point or feedback

 

signal.

 

 

 

 

 

 

 

Pr. 136

Sleep Period

Unit: 0.1sec

 

 

Settings

0.0 to 6550.0 sec

Factory Setting: 0.0

 

 

 

 

 

Pr. 137

Sleep Frequency

Unit: 0.10Hz

 

 

Settings

0.00 to 400.0 Hz

Factory Setting: 0.0

 

 

 

 

 

Pr. 138

Wake Up Frequency

Unit: 0.10Hz

 

 

Settings

0.00 to 400.0 Hz

Factory Setting: 0.0

 

 

 

 

 

These parameters determine the sleep functions of the AC drive. If the command frequency falls below the sleep frequency, for the specified time in Pr.136, then drive output is turned off until the command frequency rises above Pr.138. Please see the below diagram.

 

Frequency Command

 

Pr. 138

 

 

 

 

 

Wake Up

 

 

Actual output frequency

 

Frequency

 

 

 

 

 

 

 

 

Pr. 137

 

 

 

 

 

 

 

 

 

 

Sleep

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

Sleep Period

 

0Hz

 

 

 

 

 

 

 

 

Pr. 136

 

Pr. 139

Treatment for Counter Attained

Factory Setting: 00

Settings 00 Continue Operation

01 Stop Immediately and display E.F.

This parameter sets the procedure for the AC drive to follow once the internal counter attains the setting value in Pr.96.

Pr. 140

External Up/Down Selection

Factory Setting: 00

Settings 00 Fixed Mode (keypad)

01By Accel or Decel Time

02Reserved

This parameter is used to change the Master Frequency externally with the Multifuction Input Terminals. If any two parameters in the group Pr.39-Pr.42 are set to 14 and 15, and Pr.140 is set to 01, the up/down frequency operation is initiated as the contact closes and according to the time of acceleration/deceleration.