Delta Electronics VFD-M manual Keypad Display is Abnormal, Phase Loss PHL, Correct wiring

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 126
Image 126
5.7 Keypad Display is Abnormal

5.7 Keypad Display is Abnormal

Abnormal display or no display

Yes

Cycle power to AC motor drive

Display normal?

No

 

Yes

AC motor drive works normally

Chapter 5 TroubleshootingCheck if all connectors are connect correctly and no noise is present

Fix connector and eliminate noise

No

Check if all connectors are connect correctly and no noise is present

Yes

AC motor drive has malfunction.

Please contact DELTA.

5.8 Phase Loss (PHL)

 

Phase loss

 

 

 

 

 

 

No

 

 

 

 

Check wiring at R, S and T terminals

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Correct wiring

Check if the screws of terminals are tightened

No

 

Tighten all screws

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

Check if the input voltage of R, S, T is unbalanced

No

Yes

Please check the wiring and power system for abnormal power

Maybe AC motor drive has malfunction or misoperation due to noise. Please contact DELTA.

Revision May 2008, ME14, SW V3.04

5-5

Page 126
Image 126
Delta Electronics VFD-M Keypad Display is Abnormal, Phase Loss PHL, Check wiring at R, S and T terminals, Correct wiring